Determining Diesel Transfer Pump Capacity For Diesel Engines And Generators

senseadmin
2 Min Read
Disclosure: This website may contain affiliate links, which means I may earn a commission if you click on the link and make a purchase. I only recommend products or services that I personally use and believe will add value to my readers. Your support is appreciated!

Often process engineers are asked to design a diesel storage and transfer system for diesel engines and diesel power generators. Where to start is often a question among process engineers. There has to be a design basis for designing such a system. Today’s blog entry addresses the design basis for design of a diesel storage and transfer system along with a solved example for such a design. Readers of my blog are welcome to convert this information into an excel spreadsheet calculation and share.

Description: Attached Image

Consider the following calculation example:

Inputs:

No. of Installed DGs: 3

No. of Working DGs: 2

Rating per DG: 1500 kW

Diesel Filling time: 1 hour (to Diesel day tank)

Transfer Pump Design Flow factor: 1.1

Diesel Day tank storage basis: 24 hours

Usable Day tank volume factor = 0.95

Main Diesel Storage Tank hold-up basis = 7 days (Note 1)

Calculations:

Diesel Flow per DG = 0.4 m3/h (from table above with vlookup function)

Total Diesel flow = 0.8 m3/h (0.4*2)

Day tank theoretical capacity per DG = 9.6 m3 (0.4*24)

Day tank working capacity per DG = 10.11 m3 (9.6 / 0.95)

Max. Diesel Consumed per day = 19.2 m3 (9.6*2) where 2 is the no. of working DGs

Max. Diesel Rate = 19.2 m3/h (19.2 / 1) where 1 is the Diesel filling time in hours

Diesel Pump Design Capacity = 21.12 m3/h (19.2*1.1)

Main Diesel Tank working Capacity = 134.4 m3 (19.2*7)

Notes:

1. For on-shore installations the total diesel storage is often considered for 7 days and for off-shore installation it is generally considered as 15 days.

2. The above example calculation considers a separate main storage tank and separate individual day tanks for individual DG sets. In many instances, the individual day tank for DGs may have a hold-up for 8 to 12 hours instead of 24 hours which would require 2 fillings per day for 12 hours hold-up and 3 fillings for 8 hours hold-up

Share This Article
Follow:
Prabhu TL is an author, digital entrepreneur, and creator of high-value educational content across technology, business, and personal development. With years of experience building apps, websites, and digital products used by millions, he focuses on simplifying complex topics into practical, actionable insights. Through his writing, Dilip helps readers make smarter decisions in a fast-changing digital world—without hype or fluff.